D600 GC

D600 GC

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Maximum Rating 600 ekW 600 ekW
Minimum Rating 600 ekW 600 ekW
Emissions/Fuel Strategy EPA Stationary Emergency EPA Stationary Emergency

Technicial Specifications

Generator Set Specifications
Maximum Rating 600 ekW 600 ekW
Minimum Rating 600 ekW 600 ekW
Emissions/Fuel Strategy EPA Stationary Emergency EPA Stationary Emergency
Voltage 480 to 600 Volts 480 to 600 Volts
Frequency 60 Hz 60 Hz
Speed 1800 rpm 1800 rpm
Duty Cycle Standby Standby
Engine Specifications
Engine Model Cat® C18 In-line 6, 4-cycle Diesel Cat® C18 In-line 6, 4-cycle Diesel
Bore 5.7 in 145 mm
Stroke 7.2 in 183 mm
Displacement 1106 in³ 18.1 l
Compression Ratio 14.5:1 14.5:1
Aspiration Turbocharged Air-to-Air Aftercooled Turbocharged Air-to-Air Aftercooled
Fuel System MEUI MEUI
Governor Type ADEM™A4 ADEM™A4
Generator Set Dimensions
Length - Maximum 196.1 in 4980 mm
Width - Maximum 73.4 in 1865 mm
Height - Minimum 79.1 in 2009 mm
Height - Maximum 100.9 in 2563 mm
Dry Weight - Genset (minimum) 8959.6 lb 4064 kg
Dry Weight - Genset (maximum) 11647 lb 5283 kg

Advantages and Features

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR500 Alternator

M-Frame Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

GCCP 1.2 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to104°F (40°C)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • UL 2200 Listed
  • ULC Certification Available

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment

  • Air Inlet System
    • Turbocharger
    • Air cleaner - Non canister, disposable
    • Aftercooler core
  • Control Panel
    • GCCP 1.2
  • Cooling System
    • Radiator sight gauge
    • Thermostats and housing
    • Coolant drain valve
    • Jacket water pump, gear driven, centrifugal
    • Blower fan and fan drive with guards
    • Radiator, package mounted
  • Exhaust System
    • Exhaust manifold - dry
  • Fuel System
    • Fuel cooler
    • Primary fuel filter w/integral water separator and secondary filter, spin on
    • Integral tank base, 24 hours, UL142
    • Engine fuel transfer pump
    • Fuel priming pump
  • Generator Set
    • Complete system designed & built at ISO 9001:2000 certified facilities
    • Factory tested to design specifications at full load conditions
    • All protective devices and control functions simulated and checked
  • Generators and Generator Attachments
    • 6 Leads
    • Voltage regulator (single phase sensing)
    • Easy access to AVR and terminals
    • Insulation system, Class H
    • Brushless, self-excited 2/3 pitch (600V uses Internal excitation (IE))
    • Terminal box, IP22 RHS facing, bottom cable entry
    • Standard winding protection for non-harsh environments with relative humidity ? 95%
    • IP23 Protection
  • Governing System
    • Cat electronic governor (ADEM A4)
  • Lube System
    • Oil filler and dipstick
    • Shallow oil pan
    • Oil filter, spin on
    • Oil cooler
    • Lubricating oil, CK-4 (10W-30)
    • Oil drain with valve
    • Fumes disposal to front of radiator
  • Mounting System
    • Includes lifting provisions and termination points for coolant and lube oil drain lines
    • Captive linear vibration isolators between base and engine-generator
  • Protection
    • Safety shutoff - High water temperature
    • Safety shutoff - Overspeed
    • Safety shutoff - Low oil pressure
  • Starting/Charging System
    • 24V, 45 Amp Charging alternator
    • 24-volt electric starting motor
  • General
    • Parts book
    • Vibration damper
    • Lifting eyes

Optional Equipment

  • Air Inlet System
    • Air cleaner (Non canister disposable)
  • Bases, Mounting & Fuel Tanks
    • Audio & visual fuel alarm (@90% fuel level)
    • Integral tank base, 24 hours, UL142
    • 5 Gallon Spill Containment
    • Overfill prevention valve
    • Fuel tank pill pipe & lockable cap
    • Wide Base - Skid
  • Circuit breaker
    • 400A LSI
    • Auxiliary contacts
    • 400A LS/I
    • 800A LSI
    • 600A LSI
    • 1200A LS/I
    • 800A LS/I
    • 600A LS/I
    • 1200A LSI
  • Control System
    • 20A GFCI (Ground Fault Circuit Interrupter)
    • Ground fault relay
    • 16 -light NFPA 99/110 Annunciator
    • Volt free contacts
    • Twist release, Red button emergency stop
    • 100A Load center
    • Product link remote monitoring hardware
    • Audible alarm Gp
    • Earth (Ground) fault relay
    • Volt free contact
    • Remote E-Stop button
    • Discrete I/O module
    • Annunciators box
    • Local annunciator
  • Exhaust System
    • 8" Muffler - 25 dBA attenuation
    • Flexible exhaust connection
    • Manifold and turbocharger guards
  • Generator
    • Space heater
    • Permanent magnet excitation (PMG) generator
  • Starting System
    • Jacket water heater
    • Standard battery set: 1000 CCA, 90 amp/hr.
    • Battery charger (UL Certified)
    • Oversize battery set, 1400 CCA, 200 amp/hr
  • General
    • Extended Service Coverage
    • Generator test report
    • CSA Certification
    • UL2200 Certification
    • Tool set
  • Circuit breakers
    • Single LSI motorised circuit breaker
    • Single LSI motorised circuit breaker
    • Auxiliary contacts
    • Neutral bar (208V)
  • Enclosures
    • E-Stop
    • Sound attenuated Level 2 enclosure (White)
    • AC & DC Source lights
    • Sound attenuated enclosure
  • Cooling System
    • Coolant heater
    • Stone guards
    • Jacket water heater with pump
  • Base / Fuel Tank
    • Audio & visual fuel alarm
  • Fuel System
    • Integral 8 hour tank base
  • Starting and Charging
    • Oversize battery set
    • Standard battery set
    • 5 Amp Battery charger
    • Battery disconnect switch
  • Certifications
    • CSA 22.2
    • UL2200 Listed
    • Seismic
  • Lube System
    • Manual sump pump
WhatsApp WhatsApp