3412C (60 Hz)

3412C (60 Hz)

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Maximum Rating 800 ekW 800 ekW
Minimum Rating 635 ekW 635 ekW
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel Consumption

Technicial Specifications

Generator Set Specifications
Maximum Rating 800 ekW 800 ekW
Minimum Rating 635 ekW 635 ekW
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel Consumption
Voltage 220 to 480 Volts 220 to 480 Volts
Frequency 60 Hz 60 Hz
Speed 1800 rpm 1800 rpm
Duty Cycle Standby, Prime Standby, Prime
Engine Specifications
Engine Model 3412C TA, V-12, 4-Stroke Water-Cooled Diesel 3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore 5.4 in 137.2 mm
Stroke 6 in 152.4 mm
Displacement 1648.86 in³ 27.02 l
Compression Ratio 13:00:01 13:00:01
Aspiration TA TA
Fuel System Pump and Lines Pump and Lines
Governor Type ADEM™ A5 ADEM™ A5
Generator Set Dimensions
Length - Maximum 162.4 in 4125 mm
Width - Maximum 78.3 in 1989 mm
Height - Maximum 75 in 1906 mm
Dry Weight - Genset (minimum) 5761 lb 12700 kg
Dry Weight - Genset (maximum) 13275 lb 6021 kg

Advantages and Features

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR500 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

One Safe Source

  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment

  • Air Inlet System
    • Air cleaner, single element canister type
    • Single element canister type
  • Control Panel
    • High coolant temperature
    • Customer data link (Modbus RTU)
    • Low coolant temperature
    • Low coolant level
    • Communications:
    • Run/auto/ stop/control
    • Engine cycle crank
    • Generator temperature monitoring module
    • Power factor (per phase & average)
    • Remote CAN annunciator
    • Serial annunciator module data link
    • DC volts
    • Frequency (Hz)
    • Operating hours.
    • Emergency stop pushbutton
    • Digital I/O module
    • Local annunciator
    • Low oil pressure
    • Oil pressure (psi, kPa or bar)
    • Emergency stop
    • Warning shutdowns:
    • Volts (L-L & L-N)
    • Remote Serial annunciator
    • Speed adjust
    • Amps (per phase & average)
    • Voltage adjust
    • EMCP 4.2B
    • Overspeed
    • coolant temperature
    • Digital Indicator for:
    • RPM
    • Accessory module data link
    • Failure to start (overcrank)
    • Controls:
    • Compatible with the following optional modules:
  • Cooling System
    • Caterpillar extended life coolant
    • Radiator with guard (sized for 50 degrees C)
    • Fan and belt guards
    • Coolant drain line with valve
  • Exhaust System
    • Stainless steel exhaust flex with ANSI style outlet flange
  • Fuel System
    • Primary and Secondary fuel filters
    • Fuel priming pump
    • Water separator
  • Generator and Attachments
    • 3 Phase sensing
    • SR4B self excited
    • Class F temperature rise
    • VR6B voltage regulator
    • Busbar termination
    • 12 Leads
    • Class H insulation
    • 2:1 Volts/Hz
    • Reactive droop
  • Governing System
    • Cat electronic governor
  • Lube System
    • Oil drain line with valve
    • Lubricating oil
    • Oil filter
  • Mounting System
    • Base, formed steel with linear vibration isolators between base and engine-generator
  • Starting / Charging System
    • Battery with rack, cables
    • 45 Amp Charging alternator
    • Fuel shutoff solenoid
    • 24 Volt starting motor
  • General
    • Paint - Caterpillar yellow except rails and radiators gloss black

Optional Equipment

  • Air Inlet System
    • Air cleaner - Dual element
    • Air cleaner - Heavy element
    • Air cleaner - single element
  • Certificates
    • EU Certification
  • Circuit breakers
    • 4 Pole Circuit breakerswith shunt trip
    • 3 Pole Circuit breakers with shunt trip
    • Power terminal strip
  • Control Panel
    • EMCP 4.3, EMCP 4.4
    • Temperature monitoring package
    • Vandal proof panel door
    • Generator running VFC
    • Earth leakage Ground fault relay
    • Common alarm/shutdown relay
  • Cooling System
    • Jacket water heater
    • Radiator duct flange
    • Radiator removal
  • Exhaust System
    • Muffler 10 dBA attenuation
    • Manifold and turbocharger guards
    • Muffler 35 dBA attenuation
    • Elbow mounting kit
    • Through wall installation kit
  • Fuel System
    • Manual fuel transfer pump
    • Automatic fuel transfer system
  • Generator and Attachments
    • Internal excitation (IE)
    • Anti-condensation heater
    • Permanent magnet excitation (PMG)
    • Oversize and premium generators
  • Governing System
    • Electronic load share
  • Lube System
    • Manual sump pump
  • Mounting System
    • Fuel tank base (1200 Ltr)
  • Special Tests / Reports
    • PGS Test report @ 1.0 power factor
    • PGS Test report @ 0.8 power factor
    • Factory witness test
  • Starting / Charging system
    • Oversize battery set
    • Battery chargers
    • Heavy duty starting system
    • Battery disconnect switch
    • Battery removal
  • Enclosures
    • DC lighting package
    • Weather protective enclosure (WP)
    • Sound attenuated enclosure (SA)
WhatsApp WhatsApp