Technicial Specifications
Maximum Rating | 175 ekW 175 ekW |
Minimum Rating | 175 ekW 175 ekW |
Emissions/Fuel Strategy | U.S. EPA Cert., Tier 3 U.S. EPA Cert., Tier 3 |
Voltage | 208 to 600 Volts 208 to 600 Volts |
Frequency | 60 Hz 60 Hz |
Speed | 1800 rpm 1800 rpm |
Duty Cycle | Standby Standby |
Engine Model | C7.1 I-6, 4-Cycle Diesel C7.1 I-6, 4-Cycle Diesel |
Bore | 4.1 in 105 mm |
Stroke | 5.31 in 135 mm |
Displacement | 427.8 in³ 7.01 l |
Compression Ratio | 16.7:1 16.7:1 |
Aspiration | Turbocharged, Air to Air Aftercooled Turbocharged, Air to Air Aftercooled |
Fuel System | Electronic, Common Rail Electronic, Common Rail |
Governor Type | ADEM™A4 ADEM™A4 |
Length - Maximum | 103.7 in 2634 mm |
Width - Maximum | 51.2 in 1300 mm |
Height - Maximum | 58.7 in 1492 mm |
Dry Weight - Genset (maximum) | 3741 lb 1697 kg |
Advantages and Features
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
M-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP 1.2 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- UL 2200 Listed
- ULC Certification Available
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment
-
Air Inlet System
- Air cleaner; light duty with disposable element
-
Control Panels
- GCCP 1.2 Control panel
-
Cooling System
- Coolant drain line with valves
- Fan drive, battery charging alternator drive
- Caterpillar extended life coolant
- Radiator and cooling fan with guards
-
Generator and Generator Attachments
- Tower panel, IP22, bottom cable entry
- IP23 Protection
- 12 Leads
- Circuit breaker, IEC, 3 pole, mounted in tower panel
- Segregated low voltage (AC/DC) wiring panel
- Voltage regulator (single phase sensing)
-
Exhaust System
- Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
-
Fuel System
- Base, formed steel with single wall integral 24-hour fuel tank
- Standard open set fuel tank/base supplied
-
Lube System
- Lubricating oil
- Oil drain line with valve
-
Mounting System
- Termination points for coolant and lube oil drain lines
- Includes lifting provision and drag points
- Captive linear vibration isolators between base and engine-generator
-
Starting / Charging System
- 24V battery with rack and cables
-
Governing System
- Mechanical and electrical governing system - model dependent
-
General
- Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment
-
Alternator System
- Permanent magnet excitation (PMG)
- Quatrature droop king
- Alternator removal
- 3 Phase sensing
- R Frame auxiliary winding: R2273L4 SE aux alt 07, aux alt 08 and aux alt 10
- Anti-condensation heater
- Optional LC Frame alternator with coastal insulation protection
-
Circuit breakers
- Padlockable breaker device
- 4 Pole 250A, 400A and 630A Circuit breakers
-
Control Panel Options
- Earth fault (2 wire only)
- Speed adjust contacts
- Panel mounted audible alarm
- Volt free contacts
- Earth leakage (2 wire only)
- Overload shutdown via breaker
- Control panel heater
- Speed adjust potentiometer
- Battery charger
- Emergency stop with key
-
Control System
- Static battery charger
- Volt free contacts for common alarm
- Volt free contacts for generator set running
- GCCP 1.2
-
Cooling System
- Low coolant temperature
- Coolant heater
- Low coolant level shutdown
-
Enclosures
- Sound attenuated level 2 enclosure
-
Mounting Options
- Electronic governor
- Silencer installation kit
- Industrial silencer removal
- Battery removal
- Residential silencer
-
Fuel Systems
- Low fuel level alarm
- Compact skidbase for open sets
- DEFRA bunded fuel tank
- Open set narrow tankbase
- Low fuel level shutdown
- Skidbase for CALG enclosure sets
- High fuel level alarm
-
Test Reports
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
-
General
- Stone guards/radiator trans flange
-
Global Certifications
- Certification for CIS
-
Power Termination
- Circuit breaker, IEC, 4 pole
-
Accessories / Miscellaneous
- Packing case - compact set
- Packing case - canopied set