ტექნიკური მახასიათებლები
Maximum Rating | 550 kVA 550 kVA |
Minimum Rating | 365 kVA 365 kVA |
Emissions/Fuel Strategy | Low Fuel, Tier 2 or 3 Low Fuel, Tier 2 or 3 |
Voltage | 208 to 600 Volts 208 to 600 Volts |
Frequency | 50 Hz 50 Hz |
Speed | 1500 rpm 1500 rpm |
Duty Cycle | Standby, Prime Standby, Prime |
Engine Model | C15 ATAAC, I-6, 4-Stroke Water-Cooled Diesel C15 ATAAC, I-6, 4-Stroke Water-Cooled Diesel |
Bore | 5.4 in 137.2 mm |
Stroke | 6.75 in 171.4 mm |
Displacement | 927.56 in³ 15.2 l |
Compression Ratio | 16.1:1 16.1:1 |
Aspiration | Air to Air Aftercooled Air to Air Aftercooled |
Fuel System | MEUI MEUI |
Governor Type | Adem™A4 Adem™A4 |
Length - Maximum | 222.7 in 5656 mm |
Width - Maximum | 90 in 2286 mm |
Height - Maximum | 93.2 in 2367 mm |
უპირატესობები და მახასიათებლები
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
A-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP1.3 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
სტანდარტული ტექნიკა
-
Air System
- Aftercooler core
- Turbocharger
- Air cleaner - Non canister disposable paper filter
-
Air Inlet
- Air cleaner
-
Control Panel
- GCCP 1.3
- GCCP 1.3
-
Cooling
- Package mounted radiator
-
Cooling System
- Radiator and cooling fan with guard
- Coolant drain line with valve
- Caterpillar extended life coolant
- Fan drive, battery charging alternator drive
-
Fuel
- Secondary fuel filters
- Fuel priming pump
- Primary fuel filter with integral water separator
-
Exhaust
- Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange for customer use - shipped loose
- Exhaust flange outlet
-
Fuel System
- Standard open set fuel tank/base supplied
- Base, formed steel with single wall integral 8-hour fuel tank
-
Generator
- IP23 Protection
- Matched to the performance and output characteristics of Cat engines
- Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
-
Generator and Attachments
- IP23 Protection
- A Frame generator - IP21 Protection
- Segregated low voltage (AC/DC) wiring panel
- Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
- Optional LC Frame generator - IP23 Protection
- Power center, IP22
- Integrated voltage regulator (IVR)
-
Power Termination
- Busbar
-
Governing System
- Cat electronic governor (ADEM A4)
-
Lube System
- Lubricating oil
- Oil drain valves
-
Mounting
- Rubber vibration isolators
-
Mounting System
- Rubber vibration isolators
-
Starting/Charging
- 24 Volt battery with rack and cables
- Batteries
- 24 volt starting motor
-
General
- Engine and alternator pre paint, Caterpillar yellow
- Paint - Caterpillar yellow except rails and radiators gloss black
აირჩიეთ ტექნიკა
-
Air Inlet System
- Single element air cleaner
- Dual element air cleaner
-
Exhaust
- Industrial, residential, critical mufflers
-
Certifications
- EU Certificate of Conformance (CE)
- Global certification for CIS
-
Generator
- Oversize and premium generators
- Anti-condensation heater
- Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
-
Power Termination
- Circuit breakers, UL listed
- Circuit breakers, IEC compliant
-
Circuit breakers
- 4 Pole (IEC-100% rated) Circuit breakers - Motorised
- 3 Pole (IEC-100% rated) Circuit breakers - Motorised
- Auxiliary contacts, circuit breaker
- 4 Pole (IEC-100% rated) Circuit breakers - Package mounted
- Padlockable circuit breaker device
- Power terminal strip
- Shunt trip for IEC circuit breaker
- 3 Pole (IEC-100% rated) Circuit breakers - Package mounted
-
Control Panels
- Protective devices: Earth fault relay ; Earth leakage Ground fault relay ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
- Remote annunciator module
- Oil temperature displays
- GCCP 1.4
- Local annunciator
- Local alarm horn
- Volt free contacts
-
Starting/Charging
- Jacket water heater
- Heavy duty starting system
- Battery chargers
- Oversize batteries
- Charging alternator
-
Cooling System
- Radiator duct flange
- Stone guards
- Low coolant temperature alarm
-
Enclosures
- Sound attenuated enclosures
- High ambient sound attenuated enclosures
-
Exhaust System
- End in/end out mufflers - 10, 25 and 35 dBA attenuation
- Manifold and turbocharger guards
- Flexible exhaust fittings
- 6 and 8 inch flange GP
- 6 and 8 inch elbow kit
- Engine mounted muffler
-
Fuel System
- Dual wall fuel tank base
- Manual fuel transfer pump
- Fuel transfer system controls
-
General
- UL 2200 package
- Automatic transfer switches (ATS)
- Narrow, wide or skid base
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- Single or dual wall sub-base fuel tanks
- EU Certificate of Conformance (CE)
- EEC Declaration of Conformity
- The following options are based on regional and product configuration:
- Single or dual wall integral fuel tanks
- CSA Certification
- Sound attenuated, weather protective or high ambient weather protective enclosure
- Integral & sub-base UL listed dual wall fuel tanks
-
Generator and Attachments
- Oversize A Frame generator
- LC frame generator
- Oversize LC frame generator
- CIP A Frame generator
- LC frame CIP generator
- Permanent magnet excitation (PMG) generator
- Space heaters
- Ingress protection
-
Lube System
- Manual sump pump
-
Mounting System
- Narrow skid base - replaces standard fuel tank base
-
Special Test / Reports
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
-
Starting / Charging System
- 5 Amp single Battery charger
- Battery disconnect switch