C13 (60 Hz)

C13 (60 Hz)

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Maximum Rating 400 ekW 400 ekW
Minimum Rating 320 ekW 320 ekW
Emissions/Fuel Strategy EPA Stationary Emerg Use EPA Stationary Emerg Use

ტექნიკური მახასიათებლები

Generator Set Specifications
Maximum Rating 400 ekW 400 ekW
Minimum Rating 320 ekW 320 ekW
Emissions/Fuel Strategy EPA Stationary Emerg Use EPA Stationary Emerg Use
Voltage 208 to 600 Volts 208 to 600 Volts
Frequency 60 Hz 60 Hz
Speed 1800 rpm 1800 rpm
Duty Cycle Standby, Prime Standby, Prime
Engine Specifications
Engine Model C13 ACERT In-line 6, 4-cycle diesel C13 ACERT In-line 6, 4-cycle diesel
Bore 5.12 in 130 mm
Stroke 6.2 in 157 mm
Displacement 763 in³ 12.5 B
Compression Ratio 16.3:1 16.3:1
Aspiration Turbocharged Air to Air Aftercooled Turbocharged Air to Air Aftercooled
Fuel System MEUI MEUI
Governor Type Adem™A4 Adem™A4
Generator Set Dimensions
Length - Maximum 186.7 in 4743 mm
Width - Maximum 79.3 in 2014 mm
Height - Maximum 84 in 2133 mm

უპირატესობები და მახასიათებლები

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

A-Frame Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

GCCP 1.3 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

UL2200 Listed; CSA 22.2; Certification of Compliance – IBC Seismic; Dual IBC & HCAI

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

სტანდარტული ტექნიკა

  • Air Inlet System
    • Turbocharger
    • Aftercooler core
    • Air cleaner; light duty with disposable paper filter
  • Starting / Charging
    • Charging alternator
    • 24 Volt electric starting motor
  • Control Panel
    • GCCP 1.3
  • Control System Controller
    • GCCP 1.3
  • Cooling System
    • Fan drive, battery charging alternator drive
    • Caterpillar extended life coolant
    • Coolant drain line with valve
    • Radiator and cooling fan with guard
  • Certification
    • EPA stationary emergency use
  • Exhaust System
    • Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange for customer use - shipped loose
  • Base / Fuel Tank
    • Audio and visual fuel alarm
  • Fuel System
    • Standard open set fuel tank/base supplied
    • Base, formed steel with single wall integral 8-hour fuel tank
  • Protection
    • Safety shutoff - Overspeed
    • Safety shutoff - Low oil pressure
    • Safety shutoff - High water temperature
  • Generator and Attachments
    • Segregated low voltage (AC/DC) wiring panel
    • Power center, IP22
    • A Frame generator - IP21 Protection
    • Integrated voltage regulator (IVR)
    • Optional LC Frame generator - IP23 Protection
    • Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
  • Governing System
    • Cat electronic governor (ADEM A4)
  • Lube System
    • Oil cooler
    • Oil drain valves
    • Lubricating oil
  • Mounting System
    • Includes lifting provisions and termination points for coolant and lube oil drain lines
    • Captive linear vibration isolators between base and engine-generator
  • Starting / Charging System
    • 24V battery with rack and cables
  • General
    • Engine and alternator pre-paint, Caterpillar yellow

აირჩიეთ ტექნიკა

  • European Certificates
    • Global Certification for CIS
    • EU Certificate of Conformance (CE)
  • Air Inlet System
    • Single element air cleaner
    • Dual element air cleaner
  • Circuit breakers
    • Padlockable circuit breaker device
    • 3 Pole (IEC-100% rated) Circuit breaker
    • Shunt trip for IEC circuit breaker
    • 4 Pole (IEC-100% rated) Circuit breaker - Motorised
    • Circuit breaker (IEC) Auxiliary contacts
    • 4 Pole (IEC-100% rated) Circuit breaker
    • Power terminal strip
    • 3 Pole (IEC-100% rated) Circuit breakers - Motorised
  • Control Panels
    • Control panel protective devices: Earth fault relay ; Earth leakage ground fault ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
    • GCCP 1.4
    • Volt free contacts
    • Local alarm modules: Local annunciator
    • Remote annunciator module
  • Cooling System
    • Radiator duct flange
    • Stone guards
    • Low coolant temperature alarm
  • Enclosures
    • Sound attenuated enclosures
    • High ambient sound attenuated enclosures
  • Exhaust System
    • Flexible 8 inch exhaust fittings
    • Mufflers - End in/end out
    • 10, 25 and 35 dBA attenuation
    • 6 and 8 inch elbow kit
    • 6 and 8 inch flange GP
  • Fuel System
    • Fuel transfer system controls
    • Manual fuel transfer pump
    • Integral dual wall fuel tank base
  • Generator and Attachments
    • LC frame generator
    • LC CIP generator
    • Space heaters
    • Ingress protection
    • A Frame oversize generator
    • Permanent magnet excitation (PMG) generator
    • A Frame CIP generator
  • Lube System
    • Manual sump pump
  • Mounting System
    • Narrow skid base
  • starting / Charging System
    • Battery disconnect switch
    • Jacket water heater
    • 5 Amp single Battery charger